Filtered by vendor Emerson Subscriptions
Total 83 CVE
CVE Vendors Products Updated CVSS v3.1
CVE-2023-51761 1 Emerson 6 Gc1500xa, Gc1500xa Firmware, Gc370xa and 3 more 2024-11-21 8.3 High
In Emerson Rosemount GC370XA, GC700XA, and GC1500XA products, an unauthenticated user with network access could bypass authentication and acquire admin capabilities.
CVE-2023-49716 1 Emerson 6 Gc1500xa, Gc1500xa Firmware, Gc370xa and 3 more 2024-11-21 6.9 Medium
In Emerson Rosemount GC370XA, GC700XA, and GC1500XA products, an authenticated user with network access could run arbitrary commands from a remote computer.
CVE-2023-46687 1 Emerson 6 Gc1500xa, Gc1500xa Firmware, Gc370xa and 3 more 2024-11-21 9.8 Critical
In Emerson Rosemount GC370XA, GC700XA, and GC1500XA products, an unauthenticated user with network access could execute arbitrary commands in root context from a remote computer.
CVE-2023-43609 1 Emerson 6 Gc1500xa, Gc1500xa Firmware, Gc370xa and 3 more 2024-11-21 6.9 Medium
In Emerson Rosemount GC370XA, GC700XA, and GC1500XA products, an unauthenticated user with network access could obtain access to sensitive information or cause a denial-of-service condition.
CVE-2023-1935 1 Emerson 10 Dl8000, Dl8000 Firmware, Roc809 and 7 more 2024-11-21 9.4 Critical
ROC800-Series RTU devices are vulnerable to an authentication bypass, which could allow an attacker to gain unauthorized access to data or control of the device and cause a denial-of-service condition.
CVE-2022-30264 1 Emerson 10 Dl8000, Dl8000 Firmware, Fb3000 Rtu and 7 more 2024-11-21 9.8 Critical
The Emerson ROC and FloBoss RTU product lines through 2022-05-02 perform insecure filesystem operations. They utilize the ROC protocol (4000/TCP, 5000/TCP) for communications between a master terminal and RTUs. Opcode 203 of this protocol allows a master terminal to transfer files to and from the flash filesystem and carrying out arbitrary file and directory read, write, and delete operations.
CVE-2022-30262 1 Emerson 4 Controlwave Micro, Controlwave Micro Firmware, Controlwave Pac and 1 more 2024-11-21 7.8 High
The Emerson ControlWave 'Next Generation' RTUs through 2022-05-02 mishandle firmware integrity. They utilize the BSAP-IP protocol to transmit firmware updates. Firmware updates are supplied as CAB archive files containing a binary firmware image. In all cases, firmware images were found to have no authentication (in the form of firmware signing) and only relied on insecure checksums for regular integrity checks.
CVE-2022-30260 1 Emerson 48 Deltav Distributed Control System Sq Controller, Deltav Distributed Control System Sq Controller Firmware, Deltav Distributed Control System Sx Controller and 45 more 2024-11-21 7.8 High
Emerson DeltaV Distributed Control System (DCS) has insufficient verification of firmware integrity (an inadequate checksum approach, and no signature). This affects versions before 14.3 of DeltaV M-series, DeltaV S-series, DeltaV P-series, DeltaV SIS, and DeltaV CIOC/EIOC/WIOC IO cards.
CVE-2022-2793 1 Emerson 1 Electric\'s Proficy 2024-11-21 5.9 Medium
Emerson Electric's Proficy Machine Edition Version 9.00 and prior is vulenrable to CWE-353 Missing Support for Integrity Check, and has no authentication or authorization of data packets after establishing a connection for the SRTP protocol.
CVE-2022-2792 1 Emerson 1 Electric\'s Proficy 2024-11-21 6.6 Medium
Emerson Electric's Proficy Machine Edition Version 9.00 and prior is vulenrable to CWE-284 Improper Access Control, and stores project data in a directory with improper access control lists.
CVE-2022-2791 1 Emerson 1 Proficy 2024-11-21 5.9 Medium
Emerson Electric's Proficy Machine Edition Version 9.00 and prior is vulnerable to CWE-434 Unrestricted Upload of File with Dangerous Type, and will upload any file written into the PLC logic folder to the connected PLC.
CVE-2022-2790 1 Emerson 1 Electric\'s Proficy 2024-11-21 5.9 Medium
Emerson Electric's Proficy Machine Edition Version 9.00 and prior is vulenrable to CWE-347 Improper Verification of Cryptographic Signature, and does not properly verify compiled logic (PDT files) and data blocks data (BLD/BLK files).
CVE-2022-2789 1 Emerson 1 Electric\'s Proficy 2024-11-21 4.7 Medium
Emerson Electric's Proficy Machine Edition Version 9.00 and prior is vulnerable to CWE-345 Insufficient Verification of Data Authenticity, and can display logic that is different than the compiled logic.
CVE-2022-2788 1 Emerson 1 Electric\'s Proficy 2024-11-21 3.9 Low
Emerson Electric's Proficy Machine Edition Version 9.80 and prior is vulnerable to CWE-29 Path Traversal: '\..\Filename', also known as a ZipSlip attack, through an upload procedure which enables attackers to implant a malicious .BLZ file on the PLC. The file can transfer through the engineering station onto Windows in a way that executes the malicious code.
CVE-2022-29965 1 Emerson 49 Deltav Distributed Control System, Deltav Distributed Control System Sq Controller, Deltav Distributed Control System Sq Controller Firmware and 46 more 2024-11-21 5.5 Medium
The Emerson DeltaV Distributed Control System (DCS) controllers and IO cards through 2022-04-29 misuse passwords. Access to privileged operations on the maintenance port TELNET interface (23/TCP) on M-series and SIS (CSLS/LSNB/LSNG) nodes is controlled by means of utility passwords. These passwords are generated using a deterministic, insecure algorithm using a single seed value composed of a day/hour/minute timestamp with less than 16 bits of entropy. The seed value is fed through a lookup table and a series of permutation operations resulting in three different four-character passwords corresponding to different privilege levels. An attacker can easily reconstruct these passwords and thus gain access to privileged maintenance operations. NOTE: this is different from CVE-2014-2350.
CVE-2022-29964 1 Emerson 48 Deltav Distributed Control System Sq Controller, Deltav Distributed Control System Sq Controller Firmware, Deltav Distributed Control System Sx Controller and 45 more 2024-11-21 5.5 Medium
The Emerson DeltaV Distributed Control System (DCS) controllers and IO cards through 2022-04-29 misuse passwords. WIOC SSH provides access to a shell as root, DeltaV, or backup via hardcoded credentials. NOTE: this is different from CVE-2014-2350.
CVE-2022-29963 1 Emerson 48 Deltav Distributed Control System Sq Controller, Deltav Distributed Control System Sq Controller Firmware, Deltav Distributed Control System Sx Controller and 45 more 2024-11-21 5.5 Medium
The Emerson DeltaV Distributed Control System (DCS) controllers and IO cards through 2022-04-29 misuse passwords. TELNET on port 18550 provides access to a root shell via hardcoded credentials. This affects S-series, P-series, and CIOC/EIOC nodes. NOTE: this is different from CVE-2014-2350.
CVE-2022-29962 1 Emerson 48 Deltav Distributed Control System Sq Controller, Deltav Distributed Control System Sq Controller Firmware, Deltav Distributed Control System Sx Controller and 45 more 2024-11-21 5.5 Medium
The Emerson DeltaV Distributed Control System (DCS) controllers and IO cards through 2022-04-29 misuse passwords. FTP has hardcoded credentials (but may often be disabled in production). This affects S-series, P-series, and CIOC/EIOC nodes. NOTE: this is different from CVE-2014-2350.
CVE-2022-29960 1 Emerson 1 Openbsi 2024-11-21 5.5 Medium
Emerson OpenBSI through 2022-04-29 uses weak cryptography. It is an engineering environment for the ControlWave and Bristol Babcock line of RTUs. DES with hardcoded cryptographic keys is used for protection of certain system credentials, engineering files, and sensitive utilities.
CVE-2022-29959 1 Emerson 1 Openbsi 2024-11-21 5.5 Medium
Emerson OpenBSI through 2022-04-29 mishandles credential storage. It is an engineering environment for the ControlWave and Bristol Babcock line of RTUs. This environment provides access control functionality through user authentication and privilege management. The credentials for various users are stored insecurely in the SecUsers.ini file by using a simple string transformation rather than a cryptographic mechanism.