Show plain JSON{"dataType": "CVE_RECORD", "dataVersion": "5.1", "cveMetadata": {"cveId": "CVE-2022-4608", "assignerOrgId": "e383dce4-0c27-4495-91c4-0db157728d17", "state": "PUBLISHED", "assignerShortName": "Hitachi Energy", "dateReserved": "2022-12-19T09:46:30.033Z", "datePublished": "2023-07-26T05:26:42.720Z", "dateUpdated": "2025-03-05T18:46:44.864Z"}, "containers": {"cna": {"affected": [{"defaultStatus": "unaffected", "product": "RTU500 series", "vendor": "Hitachi Energy", "versions": [{"status": "affected", "version": "RTU500 series CMU Firmware version 13.3.1"}, {"status": "affected", "version": "RTU500 series CMU Firmware version 13.3.2"}, {"status": "unaffected", "version": "RTU500 series CMU Firmware version 13.3.3"}, {"status": "unaffected", "version": "RTU500 series CMU Firmware version 13.4.1"}]}], "configurations": [{"lang": "en", "supportingMedia": [{"base64": false, "type": "text/html", "value": "RTU500 series with HCI IEC 60870-5-104 and IEC 62351-3 configured and enabled.\n\n<br>"}], "value": "RTU500 series with HCI IEC 60870-5-104 and IEC 62351-3 configured and enabled."}], "descriptions": [{"lang": "en", "supportingMedia": [{"base64": false, "type": "text/html", "value": "A vulnerability exists in HCI IEC 60870-5-104 function included in certain versions of the RTU500 series product. The vulnerability can only be exploited, if the HCI 60870-5-104 is configured with support for IEC 62351-3. After session resumption interval is expired an RTU500 initiated update of session parameters causes an unexpected restart due to a stack overflow."}], "value": "A vulnerability exists in HCI IEC 60870-5-104 function included in certain versions of the RTU500 series product. The vulnerability can only be exploited, if the HCI 60870-5-104 is configured with support for IEC 62351-3. After session resumption interval is expired an RTU500 initiated update of session parameters causes an unexpected restart due to a stack overflow."}], "impacts": [{"capecId": "CAPEC-100", "descriptions": [{"lang": "en", "value": "CAPEC-100 Overflow Buffers"}]}], "metrics": [{"cvssV3_1": {"attackComplexity": "LOW", "attackVector": "NETWORK", "availabilityImpact": "HIGH", "baseScore": 7.5, "baseSeverity": "HIGH", "confidentialityImpact": "NONE", "integrityImpact": "NONE", "privilegesRequired": "NONE", "scope": "UNCHANGED", "userInteraction": "NONE", "vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H", "version": "3.1"}, "format": "CVSS", "scenarios": [{"lang": "en", "value": "GENERAL"}]}], "problemTypes": [{"descriptions": [{"cweId": "CWE-787", "description": "CWE-787 Out-of-bounds Write", "lang": "en", "type": "CWE"}]}], "providerMetadata": {"orgId": "e383dce4-0c27-4495-91c4-0db157728d17", "shortName": "Hitachi Energy", "dateUpdated": "2024-09-24T15:33:42.351Z"}, "references": [{"tags": ["vendor-advisory"], "url": "https://publisher.hitachienergy.com/preview?DocumentID=8DBD000121&LanguageCode=en&DocumentPartId=&Action=Launch"}], "solutions": [{"lang": "en", "supportingMedia": [{"base64": false, "type": "text/html", "value": "Update to CMU Firmware versions 13.3.3 or 13.4.1.\n\n<br>"}], "value": "Update to CMU Firmware versions 13.3.3 or 13.4.1."}], "source": {"discovery": "UNKNOWN"}, "workarounds": [{"lang": "en", "supportingMedia": [{"base64": false, "type": "text/html", "value": "Disable the HCI IEC 60870-5-104 function or its IEC 62351-3 feature if it is not used.\n\n<br>"}], "value": "Disable the HCI IEC 60870-5-104 function or its IEC 62351-3 feature if it is not used."}], "x_generator": {"engine": "Vulnogram 0.1.0-dev"}}, "adp": [{"providerMetadata": {"orgId": "af854a3a-2127-422b-91ae-364da2661108", "shortName": "CVE", "dateUpdated": "2024-08-03T01:41:45.792Z"}, "title": "CVE Program Container", "references": [{"url": "https://search.abb.com/library/Download.aspx?DocumentID=8DBD000121&LanguageCode=en&DocumentPartId=&Action=Launch", "tags": ["x_transferred"]}]}, {"metrics": [{"other": {"type": "ssvc", "content": {"timestamp": "2025-03-05T18:38:26.416457Z", "id": "CVE-2022-4608", "options": [{"Exploitation": "none"}, {"Automatable": "yes"}, {"Technical Impact": "partial"}], "role": "CISA Coordinator", "version": "2.0.3"}}}], "title": "CISA ADP Vulnrichment", "providerMetadata": {"orgId": "134c704f-9b21-4f2e-91b3-4a467353bcc0", "shortName": "CISA-ADP", "dateUpdated": "2025-03-05T18:46:44.864Z"}}]}}