Show plain JSON{"configurations": [{"nodes": [{"cpeMatch": [{"criteria": "cpe:2.3:o:siemens:logo\\!_8_bm_firmware:*:*:*:*:*:*:*:*", "matchCriteriaId": "2FA7BA89-3BF0-4C68-AC47-951B1F11F96D", "versionEndExcluding": "8.3", "vulnerable": true}], "negate": false, "operator": "OR"}, {"cpeMatch": [{"criteria": "cpe:2.3:h:siemens:logo\\!_8_bm:-:*:*:*:*:*:*:*", "matchCriteriaId": "59947FF6-3711-47C1-B91E-87DBF31DAF57", "vulnerable": false}], "negate": false, "operator": "OR"}], "operator": "AND"}], "descriptions": [{"lang": "en", "value": "A vulnerability has been identified in LOGO! 8 BM (incl. SIPLUS variants) (All versions < V8.3). The implemented encryption for communication with affected devices is prone to replay attacks due to the usage of a static key. An attacker could change the password or change the configuration on any affected device if using prepared messages that were generated for another device."}, {"lang": "es", "value": "Se ha identificado una vulnerabilidad en LOGO! 8 BM (incluyendo variantes SIPLUS) (Todas las versiones anteriores a V8.3). El cifrado implementado para la comunicaci\u00f3n con los dispositivos afectados es propenso a reproducir ataques debido al uso de una clave est\u00e1tica. Un atacante podr\u00eda cambiar la contrase\u00f1a o cambiar la configuraci\u00f3n en cualquier dispositivo afectado si usa mensajes preparados que se generaron para otro dispositivo"}], "id": "CVE-2020-25229", "lastModified": "2024-11-21T05:17:42.660", "metrics": {"cvssMetricV2": [{"acInsufInfo": false, "baseSeverity": "MEDIUM", "cvssData": {"accessComplexity": "LOW", "accessVector": "NETWORK", "authentication": "NONE", "availabilityImpact": "NONE", "baseScore": 5.0, "confidentialityImpact": "NONE", "integrityImpact": "PARTIAL", "vectorString": "AV:N/AC:L/Au:N/C:N/I:P/A:N", "version": "2.0"}, "exploitabilityScore": 10.0, "impactScore": 2.9, "obtainAllPrivilege": false, "obtainOtherPrivilege": false, "obtainUserPrivilege": false, "source": "nvd@nist.gov", "type": "Primary", "userInteractionRequired": false}], "cvssMetricV31": [{"cvssData": {"attackComplexity": "LOW", "attackVector": "NETWORK", "availabilityImpact": "NONE", "baseScore": 7.5, "baseSeverity": "HIGH", "confidentialityImpact": "NONE", "integrityImpact": "HIGH", "privilegesRequired": "NONE", "scope": "UNCHANGED", "userInteraction": "NONE", "vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:H/A:N", "version": "3.1"}, "exploitabilityScore": 3.9, "impactScore": 3.6, "source": "nvd@nist.gov", "type": "Primary"}]}, "published": "2020-12-14T21:15:19.800", "references": [{"source": "productcert@siemens.com", "tags": ["Vendor Advisory"], "url": "https://cert-portal.siemens.com/productcert/pdf/ssa-480824.pdf"}, {"source": "af854a3a-2127-422b-91ae-364da2661108", "tags": ["Vendor Advisory"], "url": "https://cert-portal.siemens.com/productcert/pdf/ssa-480824.pdf"}], "sourceIdentifier": "productcert@siemens.com", "vulnStatus": "Modified", "weaknesses": [{"description": [{"lang": "en", "value": "CWE-321"}], "source": "productcert@siemens.com", "type": "Secondary"}, {"description": [{"lang": "en", "value": "CWE-798"}], "source": "nvd@nist.gov", "type": "Primary"}]}