Filtered by vendor Schneider-electric Subscriptions
Total 795 CVE
CVE Vendors Products Updated CVSS v3.1
CVE-2011-3330 1 Schneider-electric 6 Monitor Pro, Opc Factory Server, Pl7 Pro and 3 more 2025-04-11 N/A
Buffer overflow in the UnitelWay Windows Device Driver, as used in Schneider Electric Unity Pro 6 and earlier, OPC Factory Server 3.34, Vijeo Citect 7.20 and earlier, Telemecanique Driver Pack 2.6 and earlier, Monitor Pro 7.6 and earlier, and PL7 Pro 4.5 and earlier, allows local users, and possibly remote attackers, to execute arbitrary code via an unspecified system parameter.
CVE-2011-4034 1 Schneider-electric 3 Citecthistorian, Citectscada Reports, Vijeo Historian 2025-04-11 N/A
Buffer overflow in the Steema TeeChart ActiveX control, as used in Schneider Electric Vijeo Historian 4.30 and earlier, CitectHistorian 4.30 and earlier, and CitectSCADAReports 4.10 and earlier, allows remote attackers to execute arbitrary code or cause a denial of service via unspecified vectors.
CVE-2012-0931 1 Schneider-electric 1 Modicon Quantum Plc 2025-04-11 9.8 Critical
Schneider Electric Modicon Quantum PLC does not perform authentication between the Unity software and PLC, which allows remote attackers to cause a denial of service or possibly execute arbitrary code via unspecified vectors.
CVE-2012-0930 1 Schneider-electric 1 Modicon Quantum Plc 2025-04-11 6.1 Medium
Cross-site scripting (XSS) vulnerability in Schneider Electric Modicon Quantum PLC allows remote attackers to inject arbitrary web script or HTML via unspecified vectors.
CVE-2012-0929 1 Schneider-electric 1 Modicon Quantum Plc 2025-04-11 7.5 High
Multiple buffer overflows in Schneider Electric Modicon Quantum PLC allow remote attackers to cause a denial of service via malformed requests to the (1) FTP server or (2) HTTP server.
CVE-2013-2782 1 Schneider-electric 2 Tburjr900, Tburjr900 Firmware 2025-04-11 N/A
Schneider Electric Trio J-Series License Free Ethernet Radio with firmware 3.6.0 through 3.6.3 uses the same AES encryption key across different customers' installations, which makes it easier for remote attackers to defeat cryptographic protection mechanisms by leveraging knowledge of this key from another installation.
CVE-2013-0657 1 Schneider-electric 1 Interactive Graphical Scada System 2025-04-11 N/A
Stack-based buffer overflow in Schneider Electric Interactive Graphical SCADA System (IGSS) 10 and earlier allows remote attackers to execute arbitrary code by sending TCP port-12397 data that does not comply with a protocol.
CVE-2011-4036 1 Schneider-electric 3 Citecthistorian, Citectscada Reports, Vijeo Historian 2025-04-11 N/A
Directory traversal vulnerability in Schneider Electric Vijeo Historian 4.30 and earlier, CitectHistorian 4.30 and earlier, and CitectSCADAReports 4.10 and earlier allows remote attackers to read arbitrary files via unspecified vectors.
CVE-2011-4861 1 Schneider-electric 3 Quantum Ethernet Module 140noe77100, Quantum Ethernet Module 140noe77101, Quantum Ethernet Module 140noe77111 2025-04-11 N/A
The modbus_125_handler function in the Schneider Electric Quantum Ethernet Module on the NOE 771 device (aka the Quantum 140NOE771* module) allows remote attackers to install arbitrary firmware updates via a MODBUS 125 function code to TCP port 502.
CVE-2013-2824 1 Schneider-electric 4 Citectscada, Powerlogic Scada, Struxureware Powerscada Expert and 1 more 2025-04-11 N/A
Schneider Electric StruxureWare SCADA Expert Vijeo Citect 7.40, Vijeo Citect 7.20 through 7.30SP1, CitectSCADA 7.20 through 7.30SP1, StruxureWare PowerSCADA Expert 7.30 through 7.30SR1, and PowerLogic SCADA 7.20 through 7.20SR1 do not properly handle exceptions, which allows remote attackers to cause a denial of service via a crafted packet.
CVE-2013-0687 1 Schneider-electric 1 Micom S1 Studio 2025-04-11 N/A
The installer routine in Schneider Electric MiCOM S1 Studio uses world-writable permissions for executable files, which allows local users to modify the service or the configuration files, and consequently gain privileges or trigger incorrect protective-relay operation, via a Trojan horse executable file.
CVE-2013-2761 1 Schneider-electric 1 Modicon M340 2025-04-11 N/A
The Schneider Electric M340 BMXNOE01xx and BMXP3420xx PLC modules allow remote authenticated users to cause a denial of service (module crash) via crafted FTP traffic, as demonstrated by the FileZilla FTP client.
CVE-2013-0655 1 Schneider-electric 1 Software Update Utility 2025-04-11 N/A
The client in Schneider Electric Software Update (SESU) Utility 1.0.x and 1.1.x does not ensure that updates have a valid origin, which allows man-in-the-middle attackers to spoof updates, and consequently execute arbitrary code, by modifying the data stream on TCP port 80.
CVE-2011-4033 1 Schneider-electric 3 Citecthistorian, Citectscada Reports, Vijeo Historian 2025-04-11 N/A
Buffer overflow in the Steema TeeChart ActiveX control, as used in Schneider Electric Vijeo Historian 4.30 and earlier, CitectHistorian 4.30 and earlier, and CitectSCADAReports 4.10 and earlier, allows remote attackers to cause a denial of service via unspecified vectors.
CVE-2011-5163 2 Mitsubishi-automation, Schneider-electric 2 Mx4 Scada, Citectscada 2025-04-11 N/A
Buffer overflow in an unspecified third-party component in the Batch module for Schneider Electric CitectSCADA before 7.20 and Mitsubishi MX4 SCADA before 7.20 allows local users to execute arbitrary code via a long string in a login sequence.
CVE-2013-2763 1 Schneider-electric 24 Modicon M340 Bmx Noc 0401, Modicon M340 Bmx Noc 0401 Firmware, Modicon M340 Bmx Noe 0100 and 21 more 2025-04-11 N/A
The Schneider Electric M340 PLC modules allow remote attackers to cause a denial of service (resource consumption) via unspecified vectors. NOTE: the vendor reportedly disputes this issue because it "could not be duplicated" and "an attacker could not remotely exploit this observed behavior to deny PLC control functions.
CVE-2011-3144 2 Aveva, Schneider-electric 3 Clearscada, Scx 67, Scx 68 2025-04-11 N/A
Cross-site scripting (XSS) vulnerability in Control Microsystems ClearSCADA 2005, 2007, and 2009 before R2.3 and R1.4, as used in SCX before 67 R4.5 and 68 R3.9, allows remote attackers to inject arbitrary web script or HTML via unspecified vectors.
CVE-2013-0664 1 Schneider-electric 3 Modicon M340, Modicon Premium, Modicon Quantum Plc 2025-04-11 N/A
The FactoryCast service on the Schneider Electric Quantum 140NOE77111 and 140NWM10000, M340 BMXNOE0110x, and Premium TSXETY5103 PLC modules allows remote authenticated users to send Modbus messages, and consequently execute arbitrary code, by embedding these messages in SOAP HTTP POST requests.
CVE-2011-3143 2 Aveva, Schneider-electric 3 Clearscada, Scx 67, Scx 68 2025-04-11 N/A
Use-after-free vulnerability in Control Microsystems ClearSCADA 2005, 2007, and 2009 before R2.3 and R1.4, as used in SCX before 67 R4.5 and 68 R3.9, allows remote attackers to cause a denial of service (crash) and possibly execute arbitrary code via unspecified long strings that trigger heap memory corruption.
CVE-2011-4035 1 Schneider-electric 3 Citecthistorian, Citectscada Reports, Vijeo Historian 2025-04-11 N/A
Cross-site scripting (XSS) vulnerability in Schneider Electric Vijeo Historian 4.30 and earlier, CitectHistorian 4.30 and earlier, and CitectSCADAReports 4.10 and earlier allows remote attackers to inject arbitrary web script or HTML via unspecified vectors.