CVE-2021-21863 1 Codesys 1 Development System 2024-11-21 7.8 High
A unsafe deserialization vulnerability exists in the ComponentModel Profile.FromFile() functionality of CODESYS GmbH CODESYS Development System 3.5.16 and 3.5.17. A specially crafted file can lead to arbitrary command execution. An attacker can provide a malicious file to trigger this vulnerability.
CVE-2020-7052 1 Codesys 15 Control For Beaglebone, Control For Empc-a\/imx6, Control For Iot2000 and 12 more 2024-11-21 6.5 Medium
CODESYS Control V3, Gateway V3, and HMI V3 before 3.5.15.30 allow uncontrolled memory allocation which can result in a remote denial of service condition.
CVE-2020-6081 1 Codesys 1 Runtime 2024-11-21 8.8 High
An exploitable code execution vulnerability exists in the PLC_Task functionality of 3S-Smart Software Solutions GmbH CODESYS Runtime 3.5.14.30. A specially crafted network request can cause remote code execution. An attacker can send a malicious packet to trigger this vulnerability.
CVE-2020-15806 1 Codesys 16 Control For Beaglebone, Control For Empc-a\/imx6, Control For Iot2000 and 13 more 2024-11-21 7.5 High
CODESYS Control runtime system before 3.5.16.10 allows Uncontrolled Memory Allocation.
CVE-2020-12069 4 Codesys, Festo, Pilz and 1 more 114 Control For Beaglebone, Control For Empc-a\/imx6, Control For Iot2000 and 111 more 2024-11-21 7.8 High
In CODESYS V3 products in all versions prior V3.5.16.0 containing the CmpUserMgr, the CODESYS Control runtime system stores the online communication passwords using a weak hashing algorithm. This can be used by a local attacker with low privileges to gain full control of the device.
CVE-2020-12068 1 Codesys 12 Control For Beaglebone, Control For Empc-a\/imx6, Control For Iot2000 and 9 more 2024-11-21 6.5 Medium
An issue was discovered in CODESYS Development System before 3.5.16.0. CODESYS WebVisu and CODESYS Remote TargetVisu are susceptible to privilege escalation.
CVE-2020-10245 1 Codesys 14 Control For Beaglebone, Control For Empc-a\/imx6, Control For Iot2000 and 11 more 2024-11-21 9.8 Critical
CODESYS V3 web server before 3.5.15.40, as used in CODESYS Control runtime systems, has a buffer overflow.
CVE-2019-9013 1 Codesys 12 Control For Beaglebone Sl, Control For Empc-a\/imx6 Sl, Control For Iot2000 Sl and 9 more 2024-11-21 8.8 High
An issue was discovered in 3S-Smart CODESYS V3 products. The application may utilize non-TLS based encryption, which results in user credentials being insufficiently protected during transport. All variants of the following CODESYS V3 products in all versions containing the CmpUserMgr component are affected regardless of the CPU type or operating system: CODESYS Control for BeagleBone, CODESYS Control for emPC-A/iMX6, CODESYS Control for IOT2000, CODESYS Control for Linux, CODESYS Control for PFC100, CODESYS Control for PFC200, CODESYS Control for Raspberry Pi, CODESYS Control RTE V3, CODESYS Control RTE V3 (for Beckhoff CX), CODESYS Control Win V3 (also part of the CODESYS Development System setup), CODESYS V3 Simulation Runtime (part of the CODESYS Development System), CODESYS Control V3 Runtime System Toolkit, CODESYS HMI V3.
CVE-2019-9012 1 Codesys 10 Control For Beaglebone Sl, Control For Empc-a\/imx6 Sl, Control For Iot2000 Sl and 7 more 2024-11-21 7.5 High
An issue was discovered in 3S-Smart CODESYS V3 products. A crafted communication request may cause uncontrolled memory allocations in the affected CODESYS products and may result in a denial-of-service condition. All variants of the following CODESYS V3 products in all versions prior to v3.5.14.20 that contain the CmpGateway component are affected, regardless of the CPU type or operating system: CODESYS Control for BeagleBone, CODESYS Control for emPC-A/iMX6, CODESYS Control for IOT2000, CODESYS Control for Linux, CODESYS Control for PFC100, CODESYS Control for PFC200, CODESYS Control for Raspberry Pi, CODESYS Control V3 Runtime System Toolkit, CODESYS Gateway V3, CODESYS V3 Development System.
CVE-2019-9010 1 Codesys 10 Control For Beaglebone Sl, Control For Empc-a\/imx6 Sl, Control For Iot2000 Sl and 7 more 2024-11-21 9.8 Critical
An issue was discovered in 3S-Smart CODESYS V3 products. The CODESYS Gateway does not correctly verify the ownership of a communication channel. All variants of the following CODESYS V3 products in all versions prior to v3.5.14.20 that contain the CmpGateway component are affected, regardless of the CPU type or operating system: CODESYS Control for BeagleBone, CODESYS Control for emPC-A/iMX6, CODESYS Control for IOT2000, CODESYS Control for Linux, CODESYS Control for PFC100, CODESYS Control for PFC200, CODESYS Control for Raspberry Pi, CODESYS Control V3 Runtime System Toolkit, CODESYS Gateway V3, CODESYS V3 Development System.
CVE-2019-9009 1 Codesys 14 Control For Beaglebone, Control For Empc-a\/imx6, Control For Iot2000 and 11 more 2024-11-21 7.5 High
An issue was discovered in 3S-Smart CODESYS before 3.5.15.0 . Crafted network packets cause the Control Runtime to crash.
CVE-2019-9008 1 Codesys 10 Control For Beaglebone, Control For Empc-a\/imx6, Control For Iot2000 and 7 more 2024-11-21 8.8 High
An issue was discovered in 3S-Smart CODESYS V3 through 3.5.12.30. A user with low privileges can take full control over the runtime.
CVE-2019-5105 1 Codesys 1 Codesys 2024-11-21 7.5 High
An exploitable memory corruption vulnerability exists in the Name Service Client functionality of 3S-Smart Software Solutions CODESYS GatewayService. A specially crafted packet can cause a large memcpy, resulting in an access violation and termination of the process. An attacker can send a packet to a device running the GatewayService.exe to trigger this vulnerability. All variants of the CODESYS V3 products in all versions prior V3.5.16.10 containing the CmpRouter or CmpRouterEmbedded component are affected, regardless of the CPU type or operating system: CODESYS Control for BeagleBone, CODESYS Control for emPC-A/iMX6, CODESYS Control for IOT2000, CODESYS Control for Linux, CODESYS Control for PLCnext, CODESYS Control for PFC100, CODESYS Control for PFC200, CODESYS Control for Raspberry Pi, CODESYS Control RTE V3, CODESYS Control RTE V3 (for Beckhoff CX), CODESYS Control Win V3 (also part of the CODESYS Development System setup), CODESYS Control V3 Runtime System Toolkit, CODESYS V3 Embedded Target Visu Toolkit, CODESYS V3 Remote Target Visu Toolkit, CODESYS V3 Safety SIL2, CODESYS Edge Gateway V3, CODESYS Gateway V3, CODESYS HMI V3, CODESYS OPC Server V3, CODESYS PLCHandler SDK, CODESYS V3 Simulation Runtime (part of the CODESYS Development System).
CVE-2019-19789 1 Codesys 3 Plcwinnt, Runtime Toolkit, Sp Realtime Nt 2024-11-21 6.5 Medium
3S-Smart CODESYS SP Realtime NT before V2.3.7.28, CODESYS Runtime Toolkit 32 bit full before V2.4.7.54, and CODESYS PLCWinNT before V2.4.7.54 allow a NULL pointer dereference.
CVE-2019-18858 1 Codesys 14 Control For Beaglebone, Control For Empc-a\/imx6, Control For Iot2000 and 11 more 2024-11-21 9.8 Critical
CODESYS 3 web server before 3.5.15.20, as distributed with CODESYS Control runtime systems, has a Buffer Overflow.
CVE-2019-16265 1 Codesys 2 Codesys, Eni Server 2024-11-21 9.8 Critical
CODESYS V2.3 ENI server up to V3.2.2.24 has a Buffer Overflow.
CVE-2019-13548 1 Codesys 13 Control For Beaglebone, Control For Empc-a\/imx6, Control For Iot2000 and 10 more 2024-11-21 9.8 Critical
CODESYS V3 web server, all versions prior to 3.5.14.10, allows an attacker to send specially crafted http or https requests which could cause a stack overflow and create a denial-of-service condition or allow remote code execution.
CVE-2019-13542 1 Codesys 10 Control For Beaglebone, Control For Empc-a\/imx6, Control For Iot2000 and 7 more 2024-11-21 6.5 Medium
3S-Smart Software Solutions GmbH CODESYS V3 OPC UA Server, all versions 3.5.11.0 to 3.5.15.0, allows an attacker to send crafted requests from a trusted OPC UA client that cause a NULL pointer dereference, which may trigger a denial-of-service condition.
CVE-2019-13538 1 Codesys 1 Codesys 2024-11-21 8.6 High
3S-Smart Software Solutions GmbH CODESYS V3 Library Manager, all versions prior to 3.5.16.0, allows the system to display active library content without checking its validity, which may allow the contents of manipulated libraries to be displayed or executed. The issue also exists for source libraries, but 3S-Smart Software Solutions GmbH strongly recommends distributing compiled libraries only.
CVE-2019-13532 1 Codesys 13 Control For Beaglebone, Control For Empc-a\/imx6, Control For Iot2000 and 10 more 2024-11-21 7.5 High
CODESYS V3 web server, all versions prior to 3.5.14.10, allows an attacker to send specially crafted http or https requests which may allow access to files outside the restricted working directory of the controller.