CVE-2022-3156 1 Rockwellautomation 1 Studio 5000 Logix Emulate 2024-11-21 7.8 High
A remote code execution vulnerability exists in Rockwell Automation Studio 5000 Logix Emulate software.  Users are granted elevated permissions on certain product services when the software is installed. Due to this misconfiguration, a malicious user could potentially achieve remote code execution on the targeted software.
CVE-2022-38744 1 Rockwellautomation 1 Factorytalk Alarms And Events 2024-11-21 7.5 High
An unauthenticated attacker with network access to a victim's Rockwell Automation FactoryTalk Alarm and Events service could open a connection, causing the service to fault and become unavailable. The affected port could be used as a server ping port and uses messages structured with XML.
CVE-2022-38743 1 Rockwellautomation 1 Factorytalk Vantagepoint 2024-11-21 8.8 High
Rockwell Automation FactoryTalk VantagePoint versions 8.0, 8.10, 8.20, 8.30, 8.31 are vulnerable to an improper access control vulnerability. The FactoryTalk VantagePoint SQL Server account could allow a malicious user with read-only privileges to execute SQL statements in the back-end database. If successfully exploited, this could allow the attacker to execute arbitrary code and gain access to restricted data.
CVE-2022-38742 1 Rockwellautomation 1 Thinmanager 2024-11-21 8.1 High
Rockwell Automation ThinManager ThinServer versions 11.0.0 - 13.0.0 is vulnerable to a heap-based buffer overflow. An attacker could send a specifically crafted TFTP or HTTPS request, causing a heap-based buffer overflow that crashes the ThinServer process. If successfully exploited, this could expose the server to arbitrary remote code execution.
CVE-2022-2848 4 Ge, Ptc, Rockwellautomation and 1 more 8 Industrial Gateway Server, Kepware Kepserverex, Opc-aggregator and 5 more 2024-11-21 9.1 Critical
This vulnerability allows remote attackers to execute arbitrary code on affected installations of Kepware KEPServerEX 6.11.718.0. Authentication is not required to exploit this vulnerability. The specific flaw exists within the handling of text encoding conversions. The issue results from the lack of proper validation of the length of user-supplied data prior to copying it to a heap-based buffer. An attacker can leverage this vulnerability to execute code in the context of SYSTEM. Was ZDI-CAN-16486.
CVE-2022-2825 4 Ge, Ptc, Rockwellautomation and 1 more 8 Industrial Gateway Server, Kepware Kepserverex, Opc-aggregator and 5 more 2024-11-21 9.8 Critical
This vulnerability allows remote attackers to execute arbitrary code on affected installations of Kepware KEPServerEX 6.11.718.0. Authentication is not required to exploit this vulnerability. The specific flaw exists within the handling of text encoding conversions. The issue results from the lack of proper validation of the length of user-supplied data prior to copying it to a stack-based buffer. An attacker can leverage this vulnerability to execute code in the context of SYSTEM. Was ZDI-CAN-18411.
CVE-2022-2465 1 Rockwellautomation 1 Isagraf Workbench 2024-11-21 8.6 High
Rockwell Automation ISaGRAF Workbench software versions 6.0 through 6.6.9 are affected by a Deserialization of Untrusted Data vulnerability. ISaGRAF Workbench does not limit the objects that can be deserialized. This vulnerability allows attackers to craft a malicious serialized object that, if opened by a local user in ISaGRAF Workbench, may result in remote code execution. This vulnerability requires user interaction to be successfully exploited.
CVE-2022-2464 1 Rockwellautomation 1 Isagraf Workbench 2024-11-21 7.7 High
Rockwell Automation ISaGRAF Workbench software versions 6.0 through 6.6.9 are affected by a Path Traversal vulnerability. Crafted malicious files can allow an attacker to traverse the file system when opened by ISaGRAF Workbench. If successfully exploited, an attacker could overwrite existing files and create additional files with the same permissions of the ISaGRAF Workbench software. User interaction is required for this exploit to be successful.
CVE-2022-2463 1 Rockwellautomation 1 Isagraf Workbench 2024-11-21 6.1 Medium
Rockwell Automation ISaGRAF Workbench software versions 6.0 through 6.6.9 are affected by a Path Traversal vulnerability. A crafted malicious .7z exchange file may allow an attacker to gain the privileges of the ISaGRAF Workbench software when opened. If the software is running at the SYSTEM level, then the attacker will gain admin level privileges. User interaction is required for this exploit to be successful.
CVE-2022-2179 1 Rockwellautomation 4 Micrologix 1100, Micrologix 1100 Firmware, Micrologix 1400 and 1 more 2024-11-21 6.5 Medium
The X-Frame-Options header in Rockwell Automation MicroLogix 1100/1400 Versions 21.007 and prior is not configured in the HTTP response, which could allow clickjacking attacks.
CVE-2022-1797 1 Rockwellautomation 18 Compact Guardlogix 5370, Compact Guardlogix 5370 Firmware, Compact Guardlogix 5380 and 15 more 2024-11-21 6.8 Medium
A malformed Class 3 common industrial protocol message with a cached connection can cause a denial-of-service condition in Rockwell Automation Logix Controllers, resulting in a major nonrecoverable fault. If the target device becomes unavailable, a user would have to clear the fault and redownload the user project file to bring the device back online.
CVE-2022-1161 1 Rockwellautomation 48 Compact Guardlogix 5370, Compact Guardlogix 5370 Firmware, Compact Guardlogix 5380 and 45 more 2024-11-21 10 Critical
An attacker with the ability to modify a user program may change user program code on some ControlLogix, CompactLogix, and GuardLogix Control systems. Studio 5000 Logix Designer writes user-readable program code to a separate location than the executed compiled code, allowing an attacker to change one and not the other.
CVE-2022-1159 1 Rockwellautomation 10 Compact Guardlogix 5380, Compact Guardlogix 5380 Firmware, Compactlogix 5380 and 7 more 2024-11-21 7.7 High
Rockwell Automation Studio 5000 Logix Designer (all versions) are vulnerable when an attacker who achieves administrator access on a workstation running Studio 5000 Logix Designer could inject controller code undetectable to a user.
CVE-2022-1118 1 Rockwellautomation 3 Connected Component Workbench, Isagraf Workbench, Safety Instrumented Systems Workstation 2024-11-21 8.6 High
Connected Components Workbench (v13.00.00 and prior), ISaGRAF Workbench (v6.0 though v6.6.9), and Safety Instrumented System Workstation (v1.2 and prior (for Trusted Controllers)) do not limit the objects that can be deserialized. This allows attackers to craft a malicious serialized object that, if opened by a local user in Connected Components Workbench, may result in arbitrary code execution. This vulnerability requires user interaction to be successfully exploited
CVE-2022-1018 1 Rockwellautomation 3 Connected Components Workbench, Isagraf, Safety Instrumented Systems Workstation 2024-11-21 5.5 Medium
When opening a malicious solution file provided by an attacker, the application suffers from an XML external entity vulnerability due to an unsafe call within a dynamic link library file. An attacker could exploit this to pass data from local files to a remote web server, leading to a loss of confidentiality.
CVE-2021-33012 1 Rockwellautomation 2 Micrologix 1100, Micrologix 1100 Firmware 2024-11-21 8.6 High
Rockwell Automation MicroLogix 1100, all versions, allows a remote, unauthenticated attacker sending specially crafted commands to cause the PLC to fault when the controller is switched to RUN mode, which results in a denial-of-service condition. If successfully exploited, this vulnerability will cause the controller to fault whenever the controller is switched to RUN mode.
CVE-2021-32960 1 Rockwellautomation 1 Factorytalk Services Platform 2024-11-21 8.5 High
Rockwell Automation FactoryTalk Services Platform v6.11 and earlier, if FactoryTalk Security is enabled and deployed contains a vulnerability that may allow a remote, authenticated attacker to bypass FactoryTalk Security policies based on the computer name. If successfully exploited, this may allow an attacker to have the same privileges as if they were logged on to the client machine.
CVE-2021-32926 1 Rockwellautomation 4 Micro800, Micro800 Firmware, Micrologix 1400 and 1 more 2024-11-21 7.5 High
When an authenticated password change request takes place, this vulnerability could allow the attacker to intercept the message that includes the legitimate, new password hash and replace it with an illegitimate hash. The user would no longer be able to authenticate to the controller (Micro800: All versions, MicroLogix 1400: Version 21 and later) causing a denial-of-service condition
CVE-2021-27476 1 Rockwellautomation 1 Factorytalk Assetcentre 2024-11-21 10 Critical
A vulnerability exists in the SaveConfigFile function of the RACompare Service, which may allow for OS command injection. This vulnerability may allow a remote, unauthenticated attacker to execute arbitrary commands in Rockwell Automation FactoryTalk AssetCentre v10.00 and earlier.
CVE-2021-27475 1 Rockwellautomation 1 Connected Components Workbench 2024-11-21 8.6 High
Rockwell Automation Connected Components Workbench v12.00.00 and prior does not limit the objects that can be deserialized. This vulnerability allows attackers to craft a malicious serialized object that, if opened by a local user in Connected Components Workbench, may result in remote code execution. This vulnerability requires user interaction to be successfully exploited.